Flushing methods with reservoir -Tipping bucket
Dimensioning and selection
For the dimensioning and selection of the drum, the manufacturer provides dimensioning diagrams that are based on the Brombach formula [FI-UFTa] (Equation A / Equation B).
(Equation A)
with:
V0 | = | Minimum required tipping bucket volume for the standard solution in l/serial m width |
L | = | Flushing lane length [m] |
Kuft | = | Shape parameter for tipping bucket UFT-FluidFlush Geometry FF10 [-] (=0.071) |
h | = | height [m] |
(Equation B)
with:
Verf | = | Minimum required tipping bucket volume in l/serial m width |
V0 | = | Minimum required tipping bucket volume for the standard solution in l/serial m width |
Ki | = | Slope coefficient [-] |
I [%] | 1 | 2 | 3 | 4 | 5 |
Ki [-] | 1,08 | 1,00 | 0,95 | 0,90 | 0,86 |
I | = | Flushing lane gradient [%] |
Ka | = |
Positioning parameter [-] (tipping backwards: Ka = 1.00 / tipping forward: Ka = 0.90)
|