11088 search results:

According to EN 752 [ [EN752:2017]], environmentally relevant analyses have the objective to determine the environmental impacts of sewage when it leaks from the drain and sewer system depending on its composition and leakage potential.

In this context, these analyses serve to detect [ [EN752:2017]]:

  • the effects of leaking drains and sewers on the ground water composition. Drains and sewers in protected or vulnerable groundwater areas that convey …

In accordance with EN 752 [ [EN752:2017]], drain and sewer systems have to be durable, fail-safe and leakproof. The latter requirement means that, in order to avoid an impermissible pollution of the groundwater or an unwanted dilution of the sewage, substances must not enter the groundwater and the groundwater must not be discharged together with the sewage.

To implement this requirement, drain and sewer systems must only be built, operated and maintained …

As a general rule, the subsequently introduced preparatory measures for the execution of a leak tightness testing apply for all methods of testing listed in (Theoretical background on leak tightness testing), Image 4‑124.

(Image: Applicable standards and regulations for leakage testing in the Federal Republic of Germany)

Planning documents

The client has to provide sufficient planning documents for the planning, preparation and execution of the leak …

Theoretical background on leak tightness testing

In all methods that are used for leak tightness testing, the measurement tasks are either limited to:

  • the acquisition of the time period within which a certain change in pressure is created, or
  • the acquisition of the required quantity of water that has to be added to keep up a constant test pressure.

That means that a certain test media loss is tolerated in all testing methods. The definition of the …

Air pressure testing

The equation that is used for air pressure testing is based on the assumption that an air mass flow escapes through a leak in a defined period of time, resulting in a reduction of pressure (also called pressure loss) in the pipe to be tested. This can be calculated under the assumption of an isentropic and adiabatic flow, that is, during the flow there is neither a loss due to friction nor is there a heat exchange between the …

Due to the different physical properties of the test media (water as an incompressible medium versus air as a compressible medium), the results of leak tightness testings with different test media cannot be directly compared to each other. The determination equations described in the text above are formulated with reference to the leakage area AL. This allows for a preparation of the results of leak tightness testings with different test media in …

Leak tightness testing of drains and sewers - Testing along entire sections

The principle of a section-wise leak tightness testing of drains and sewers is illustrated in Image 4‑128. The section is blocked at both ends by means of sealing elements that are equipped with connections for compressed air to inflate the individual rubber seals of the sealing elements, to fill the test volume with the test medium, to ensure its venting as well as for pressure …

Pressure testing using water as the test medium represents the classical method of leak tightness testing ( (Theoretical background on leak tightness testing)).

If the water loss during testing exceeds the permissible limit value, the causes have to be identified and eliminated. Then, the test is to be repeated (Image 4‑143).

(Image: Flow chart Water pressure testing – Method “W” in accordance with EN 1610)

In the context of the limiting conditions …

Compared to water pressure testing, leak tightness testing with air as the test medium ( (Air pressure testing, Vacuum testing)) has the following advantages [ [FI-Hydro]]:

  • The test section is not filled with water, but with air, so that there are no problems related to water supply and water damages due to sudden pipe breaks.
  • Irrespective of the gradient the whole test section is put under a constant test pressure.
  • Fast installation of the test …

In leak tightness testing ( (Air pressure testing, Vacuum testing)), a vacuum (negative pressure) is applied to the sewer section or the part of the sewer section to be tested. If there exists a leakage, an increase in pressure (∆p) will occur that, amongst other things, depends on the type and extent of the damage as well as on the type of medium that enters the sewer section through the damaged spot (air, water or a mix of both).

Compared to leak …

For sewers operated under gravity, the leak tightness testing explained in previous sections can be replaced by a visual “testing for infiltration with case-related specifications” by means of a visual inspection ( (Direct visual inspection of drains and sewers)) or a sewer TV inspection ( (Indirect visual inspection of drains and sewers)), if the groundwater level is demonstrably above the pipe crown. Suggestions for the verification of the groundwater …

A special form of testing for infiltration is the infiltration measurement: This method is standardised in the USA in the ASTM-Standard C 1091-90 – 03a (2008) Standard “Test Method for Hydrostatic Infiltration Testing of Vitrified Clay Pipe Lines” [ [ASTMC109190]] for the final acceptance of newly laid gravity sewers made of vitrified clay.

The test according to [ [ASTMC109190]] is carried out on backfilled piping under the condition that the groundwater …

The method of leak tightness testing for individual sectors of sewer sections is applied analogously to section-wise leak tightness testing ( (Leak tightness testing of drains and sewers – Testing of sockets)). The sealing elements, for example, are connected to each other by means of a chain that is adjusted in its length to the length of the sector to be tested and pulled into the required position either manually or by means of a cable winch (…

In the testing or final acceptance of existing or recently rehabilitated drains and sewers, section-wise leak tightness testing is not always economically viable or technically possible. The reasons can be found, for example, in the existence of integrated building connections or connection sewers for non-accessible cross sections, the need for a large water quantity to fill the entire section in the case of larger, man-accessible cross sections …

In EN 1610 [ [DINEN1610: 2015]], the testing of joints with water as the test medium is only described for newly laid or recently rehabilitated drains and sewers. According to that standard, the testing of joints has the same test requirements, i.e. the same water addition values and testing times, as in section- or sector-wise leak tightness testing (Image 4‑164).

(Image: Leak tightness testing of individual pipe joints in newly laid or recently …

In leak tightness testing by means of a compressible medium under pressure (e.g. air), the pressure decay does not only depend on the geometrical dimensions of the leakage, but primarily on the air volume within the section under test and the testing time. These dependencies are also the same for leak tightness testing by means of vacuum. Thus, test results that have been achieved that way are only significant and comparable, if they are referenced …

In the context of the inspection and acceptance of rehabilitated locally limited areas of damage in man-accessible sewers (e.g. cracks before and after sealing by means of injection), it can make sense to carry out leak tightness testing only in the affected areas. A suitable, tried and tested testing device is shown in Image 4‑166.

(Image: Device used for leak tightness testing’s of locally limited areas of damage in man-accessible sewers )

It is …

Regarding the inspection of newly laid or recently rehabilitated manholes and inspection chambers and their pipe connections EN 1610 [ [DINEN1610: 2015]] applies in Europe and DWA-A 139 [ [DWAA139:2019]] in Germany. The inspection itself is solely based on water as the test medium. This results from the fact that it is impossible to define conditions for testing with either air or vacuum that have the same leak tightness requirements for manholes …

Testing of road catch basins

At the current time, there are still no rules and regulations for leak tightness testing in road catch basins (section 1.6). The following remarks are based on the results of a research project that has been carried out in 2008 on behalf of the Stiftung Industry research centre (Cologne) [ [Stein2008]] with the target to close that gap. The test methods and criteria that are determined in the standard regulations for drains, …

Basically, leak tightness testing for connection sewers is comparable to that for drains and sewers ( (Leak tightness testing of drains and sewers – Testing along entire sections)). Tests can be done either with air or water. The type of the test medium to be used is determined by the client. Due to the generally large difference in height between the lowest and the highest point of the individual pipe, the test should preferably be carried out with …